SFJ-231 Helium Mass Spectrometry Leak Detector Equipment for GIS Leak Detection
Helium mass spectrometer leak detector is an instrument for rapid positioning and quantitative measurement of leakage of sealed containers.
Parameters of SFJ-231 Helium Leak Detector
Product Name | Helium Leak Detector SFJ-231 |
Diamension | 645*678*965mm |
Operating temperature | 0~40°C |
Detectable Quality | 2, 3, 4 (H2, He3, He4) |
User Interface | 7inch Color Touch Screen |
Detection Method | Helium Leak Detection |
Mini Leak Detection Rate(Pa.m3/s)/Vaccum Mode | 5*10-13 Pa·m3/s |
Communication Interface | RS232/485, USB*2 |
Max Allowable Leak Detection Pressure (Pa) | 1500 |
Ion Source | 2pcs, Iridium Coated Yttrium Oxide, Automatic Switching |
Main Features | Mass Spectrometer Leak Detector, Helium mass spectrometer Leak Detector, helium leak testing |
Mini Leak Detection Rate(Pa.m3/s)/Sniffer Mode | 5*10-9 Pa·m3/s |
Start Time | 2min |
Leak Detection Port | DN25KF |
Power | AC220V, 50Hz/60Hz |
Language | Chinese/English |
Application of SFJ-231 Helium Mass Spectrometer Leak Detector in High-Voltage GIS Equipment / SF₆ Gas Tightness Testing in the Power Industry
1. Background and Principle
High-voltage Gas Insulated Switchgear (GIS) uses SF₆ gas as an
insulating and arc-quenching medium. Its sealing integrity directly
affects insulation performance, arc-extinguishing capability, and
operational safety. SF₆ leakage can lead to reduced insulation
strength, arc-quenching failure, and even equipment breakdown.
Helium mass spectrometry leak detection is a core method for GIS
sealing tests due to helium’s (He) small molecular size, high
permeability, non-reactivity with SF₆, and the ultra-high
sensitivity of the SFJ-231 leak detector (minimum detectable leak
rate: 5.0×10⁻¹³ Pa・m³/s in vacuum mode). By using helium as a
tracer gas, the detector captures helium signals to locate leaks
and quantify leak rates.
2. Leak Detection Methods (Based on SFJ-231 Specifications)
The SFJ-231 helium leak detector supports vacuum mode (higher
sensitivity) and sniffer mode (convenient for pressurized systems,
max allowable pressure: 1500 Pa).
Vacuum Mode Leak Detection (Higher Sensitivity, Requires Evacuated
GIS)
Application: Newly installed, overhauled, or disassembled GIS (where internal
SF₆ is removed and vacuum can be applied).
Principle:
Vacuum Mode Procedure
Gas Path Connection: Link GIS chamber → SFJ-231 (DN25KF) → vacuum pump
(pressure-resistant hoses).
Evacuation: Pump down to ≤1 Pa (lower pressure = better sensitivity).
Detection Settings: Set to vacuum mode, adjust response time (<1s), alarm threshold
(per DL/T 596-2021).
Helium Spray Test: Spray helium (5-10mm from the detection point, stay for 3-5s, and
observe the signal using the response time of SFJ-231<1s) at a
suspicious point (in the order of marking) on the outside of the
GIS equipment. If the leak detector shows a sudden increase in the
leak rate (synchronized change of numbers and curves), it means
that the point is a leak point, and record the leak rate value.
Then re-inspection and confirmation.
![]() |